by MASTER

Verify fuel level and perform a brief test-start to confirm readiness; run this monthly and after any extended operation or fuel delivery. Use this routine when the generator has not been recently checked or a log entry is missing.

Fecit 앱에 저장하기
이 루틴을 Fecit 앱에서 열어 내 라이브러리에 추가하세요.

내용 미리보기

Emergency generator fuel check and test-start log

Verify fuel level and perform a brief test-start to confirm readiness; run this monthly and after any extended operation or fuel delivery. Use this routine when the generator has not been recently checked or a log entry is missing.

⏱ 30분 ★ 보통
현재

Fuel level and battery condition are not known and there is no recent test-start entry in the generator log.

난관

Fuel gauges can be unreliable and tank access may be cramped or dirty, making an accurate measurement harder; test-starts must be scheduled to avoid transferring loads unexpectedly and require someone to monitor engine parameters during the run.

기대

Fuel level, battery voltage, and basic engine readings are recorded in the log and a completed test-start entry shows the generator ran for the planned test duration without critical faults.

도구
  • • Flashlight — 1
  • • Fuel dipstick or calibrated measuring rod — 1
  • • Multimeter — 1
  • • Pen — 1
  • • Logbook — 1
단계
  1. 01
    Prepare site and safety check
    Confirm generator area is clear and safe, notify operations, wear PPE, set generator selector to OFF or MANUAL as required, and gather tools; record start time placeholder in log.
    ⏱ 5분
  2. 02
    Measure and record fuel level
    Open tank access, read the installed fuel gauge, verify with dipstick or measuring rod if gauge is suspect, convert measurement to liters or percentage, and write the exact value and time in the log.
    ⏱ 5분
  3. 03
    Inspect battery and electrical connections
    Measure battery voltage with the multimeter, inspect terminals for corrosion and tightness, note voltage (e.g., 12.6 V) and any terminal issues in the log.
    ⏱ 5분
  4. 04
    Perform test-start and observe
    Start the generator in test mode, run for 10 minutes while monitoring oil pressure, coolant temperature, exhaust smoke and audible abnormalities, record start time, runtime and any fault codes or anomalies in the log; stop if a critical fault appears.
    ⏱ 10분
  5. 05
    Complete log and secure equipment
    Enter final details: fuel reading, battery voltage, start/stop times, observations and actions taken; close tank access, stow tools, and confirm normal selector position for standby operation.
    ⏱ 5분